Reactor
protection
Most automatic capacitor
banks employed today are provided with reactor protection as a result of the increasing
harmonic loading of the consumer installation and the power networks. Every
capacitor or capacitor tap is connected in series to an inductance (reactor),
in contrast to "normal" unprotected compensation.
If the resonant frequency of the series resonant
circuit formed in this way ( capacitors and Inductor) deviates (is lower) by
more than 10% from the frequency of the nearest harmonic, then one speaks of a detuned resonator
circuit or an anti-resonance circuit. Reactor protected
compensation systems are designed as detuned resonator circuits and the series
resonant frequency f0 is normally chosen to be below the frequency
of the 5th harmonic (250 Hz). The capacitor and reactor system is therefore
inductive for all harmonic frequencies ³ 250 Hz and dangerous resonance
between the capacitor and network inductance (e.g. transformer) is therefore
avoided. Consumer installations with
high 3rd harmonic (150 Hz) components are an exception but it can
become necessary to set the series resonant frequency to 134 Hz in such cases.
The graph above shows the
frequency response of 5.67%; 7% and 14% detuned circuits. It should be noted
that the closer the resonant frequency of the anti-resonance filter is to the Harmonic
to be filtered, lower is the impedance offered and therefore better is the
filtering effect. For example 5.67% which is tuned at 210Hz will have lower
impedance to the 5th harmonic compared to the 7% detuned which has a
resonance frequency of 189Hz. This is shown by the points on each curve at
250Hz. Below table shows the amount of harmonic current that will be absorbed
in each case.
Detuning
|
Resonant
Frequency
|
% of 5th
Harmonic current absorbed
|
5.67%
|
210 Hz
|
30~50%
|
7%
|
189 Hz
|
10-20%
|
14%
|
134 Hz
|
0%
|
From the above table it is
clear that depending on the load profile and also the duty cycle of the
non-linear loads the proper selection of the detuning frequency should be made.
Please consider that using 7% detuned
system may not be always helpful and high distortion may still persist on the
load busbars.
If the series resonant
frequency is between 10% below or above a harmonic frequency, then it is described
as a tuned resonator circuit. Tuned resonator circuits
are normally employed as wave traps for the deliberate
reduction of individual harmonics.
Reactor
protection-factor p
The reactor-protection
factor p [%] specifies the ratio of the reactor reactance to the capacitor reactance
at network frequency.
p=XLx 100 / Xc
The resonant frequency of the series
resonant circuit can also be calculated from p using the following equation:
fres = f1 x (1/sqrt(p))
For example: p=7 %, f1 =
50 Hz
fres = 50 x (1/sqrt(0.07)) = 189Hz
One of the often-tried
standard values is normally used for the choice of a suitable
reactor-protection factor for the application:
Reactor-protection
factor
p
|
Series
resonant
frequency
fR
|
5%
|
223 Hz
|
5.67%
|
210 Hz
|
7%
|
189 Hz
|
8%
|
177 Hz
|
12.5%
|
141 Hz
|
14%
|
134 Hz
|
Capacitor
rated voltage with reactor protection
A voltage increase arises
at the capacitor from the serial connection of the reactor and capacitor. It
can be calculated from the reactor-protection factor p:
For example: p = 7%, UN
= 440 V
Uc =Un(1/(1-p))
Uc= 400(1/(1-0.07)) = 473V
The capacitors employed for
p = 7% must therefore be suitable for a continuous rated voltage of at least 480
V. Here, you must always be careful
about the voltage tolerance for the nominal net voltage.
When the voltage on the
capacitors increase the KVAr output of the capacitor bank also changes. This is
given by the following equation.
Qc=(1-p/100).[(Uc^2)/ (Un^2)] .Qn
In such a case case it is necessary to use adjustable ratings. For more information please read the reactor application note from Electronicon System Electric . or read the entry for calculations.
No comments:
Post a Comment