In this section I shall try to give instructions to select a detuned reactor (reactor -capacitor combination)
The table below is given in format which allows reader to print and use it as it is.
Steps
|
Fill Below
|
Remarks/Actions
|
1.
Network voltage
|
||
2.
Frequency
|
For 60Hz. Contact us directly.
|
|
3. Harmonic spectrum is
known
|
||
3rd
|
14% detuning if 3rd present
|
|
5th
|
7% to 5.6% if 5th present
|
|
7th
|
||
9th
|
||
4. Harmonic currents
are known
|
Go to 5th step
|
|
Ih >
1.5 In
|
Consult Specialist
|
|
1.3In > Ih > I.5In
|
5.67%
|
|
1.1In > Ih > I.3In
|
7%
|
|
5.
Resonant conditions
exists
|
Select 7%
|
|
6. No info on Harmonic
currents
|
Select 7%
|
|
7.
Select compensation
steps
|
||
8.
Adjusted or
non-adjusted
|
See example calculations below
|
|
9.
Reactor material
|
Recommend Aluminium
|
|
10.
Linearity
|
Standard or customised.
|
|
11.
Terminations
|
||
12.
Thermal cutouts
|
Recommended
|
|
Selection complete. Refer PFC components Catalogue
for part numbers.
|
25 kvar 440 V 50Hz 3 x 137uF (411uF)
To be detuned to 189Hz (7%)
Selection of the reactor-
25 kvar 440 V 50Hz 3 x 137uF (411uF)
To be detuned to 189Hz (7%)
Using the above methods it is easily possible to arrive at the correct values for the detuned combination.
For more information please visit Electronicon-SE or contact us directly.